Home > News > Industry news > Attention in Radiator Ventilatio of Gene…

Attention in Radiator Ventilatio of Geneset

Attention in Radiator Ventilatio of Geneset

  Air inlet baffle and shutters should be able to adjust  the gas flow during operation (such as narrow blade   shutter assemblies with greater resistance than wide).

   When the geneset is out of service in the cold climate, the automatic switch should close the air inlet and outlet; when the  geneset is running,the thermostat valve should be partially opened to allow part of the air to circulate and reduce the intake of cold air. When the geneset starts, the inlet&outlet on-off valves should all be opened: when the temperature is higher than 60°F (16°C), the circulation control valve should be all closed.

   Except for the the high and cold climate, the engine room allows the circulation of heat dissipation airflowthe other ventilation airflow should be directly discharged outdoors, and it is strictly forbidden to heat other rooms 

(except the generator room).

   The radiator must use flexible pipe joints to absorb  the displacement and vibration of the  geneset to prevent noise transmission.

  The baffle should be added near the ventilation    inlets and outlets to reduce fan noise and weaken the adverse effect of external wind force.

 


Scan the qr codeClose
the qr code